See All Acoustic End-of-Line Test Systems See All DAQ and instruments See All Electroacoustics See All Software See All Transducers See All Vibration Testing Equipment See All Academy See All Resource Center See All Applications See All Industries See All Insights See All Services See All Support See All Our Business See All Our History See All Our Sustainability Commitment See All Global Presence
arrow_back_ios

Main Menu

See All Actuators See All Combustion Engines See All Durability See All eDrive See All Transmission & Gearboxes See All Turbo Charger See All DAQ Systems See All High Precision and Calibration Systems See All Industrial electronics See All Power Analyser See All S&V Hand-held devices See All S&V Signal conditioner See All Accessories See All DAQ Software See All Drivers & API See All nCode - Durability and Fatigue Analysis See All ReliaSoft - Reliability Analysis and Management See All Test Data Management See All Utility See All Vibration Control See All Acoustic See All Current / voltage See All Displacement See All Load Cells See All Pressure See All Strain Gauges See All Torque See All Vibration See All LDS Shaker Systems See All Power Amplifiers See All Vibration Controllers See All Accessories for Vibration Testing Equipment See All Training Courses See All Whitepapers See All Acoustics See All Asset & Process Monitoring See All Custom Sensors See All Data Acquisition & Analysis See All Durability & Fatigue See All Electric Power Testing See All NVH See All Reliability See All Smart Sensors See All Vibration See All Weighing See All Automotive & Ground Transportation See All Calibration See All Installation, Maintenance & Repair See All Support Brüel & Kjær See All Release Notes See All Compliance See All Our People
arrow_back_ios

Main Menu

See All CANHEAD See All GenHS See All LAN-XI See All MGCplus See All Optical Interrogators See All QuantumX See All SomatXR See All Fusion-LN See All Accessories See All Hand-held Software See All Accessories See All BK Connect / Pulse See All API See All Microphone Sets See All Microphone Cartridges See All Acoustic Calibrators See All Special Microphones See All Microphone Pre-amplifiers See All Sound Sources See All Accessories for acoustic transducers See All Experimental testing See All Transducer Manufacturing (OEM) See All Accessories See All Non-rotating (calibration) See All Rotating See All CCLD (IEPE) accelerometers See All Charge Accelerometers See All Impulse hammers / impedance heads See All Cables See All Accessories See All Electroacoustics See All Noise Source Identification See All Environmental Noise See All Sound Power and Sound Pressure See All Noise Certification See All Industrial Process Control See All Structural Health Monitoring See All Electrical Devices Testing See All Electrical Systems Testing See All Grid Testing See All High-Voltage Testing See All Vibration Testing with Electrodynamic Shakers See All Structural Dynamics See All Machine Analysis and Diagnostics See All Process Weighing See All Calibration Services for Transducers See All Calibration Services for Handheld Instruments See All Calibration Services for Instruments & DAQ See All On-Site Calibration See All Resources See All Software License Management
November 21, 2022


Annoyance from low-frequency noise is increasingly recognized as a problem in multi-family residential buildings. Unfortunately, low-frequency sound insulation is difficult to determine accurately, particularly in smaller rooms such as bedrooms – precisely the kinds of rooms where low-frequency noise is most likely to cause annoyance.

To address this need, ISO 16283 introduced additional procedures for sound insulation measurements below 100 Hz where the source or receiver rooms are smaller than 25 m3. These new procedures are performed in addition to the standard measurements and are used to adjust bands below 100 Hz in sound insulation calculations.

 

For level measurements, the low-frequency procedure requires additional measurements in four corners of the room, two of which should be at floor level and the other two at ceiling level. The highest level in any corner is then determined for each frequency band and combined with the average levels from the standard procedure in a weighted average. The background correction for level measurements in the receiving room is also different to the standard procedure, with background measurements made in each corner and used to individually correct the corresponding corner level measurement.

For an airborne partition where both the source and receiving rooms are smaller than 25 m3, the low-frequency procedure requires 20 additional level measurement positions. Combined with the requirements to treat each band separately, and to individually correct receiving room levels for background noise, the low-frequency procedure adds substantial bookkeeping to a project. Thankfully, Building Acoustics Partner handles all this bookkeeping for the user. The procedure is automatically triggered when needed, and intelligently integrated into the standard workflow. HBK 2255’s rigid microphone extension rod also makes it easy and safe to measure in room corners.

 

When the receiving room is smaller than 25 m3, there is also a low-frequency procedure for reverberation time measurements. The low-frequency reverberation time procedure requires that the 63 Hz 1/1-octave band is measured instead of the 50 Hz, 63 Hz and 80 Hz 1/3-octave bands. This single 1/1-octave band reverberation time is used instead of the 1/3-octave band values in the calculation of DnT and/or R'. The requirements for source and microphone positions are the same as for the standard reverberation time measurements.

 

HBK 2255 and Building Acoustics Partner implements the low-frequency procedure for reverberation time without any extra effort from the user. Instead of measuring all reverberation time positions separately for 1/1- and 1/3-octave bandwidths, HBK 2255 can measure reverberation time for both bandwidths simultaneously, halving the number of reverberation time measurements needed. The app automatically replaces the 50 Hz, 63 Hz and 80 Hz 1/3-octave reverberation time values with the 63 Hz 1/1-octave reverberation time when required.

 

The low-frequency procedure in ISO 16283 undoubtedly improves the reliability of low-frequency sound insulation measurements in small rooms but adds substantial complexity to the measurement procedure, bookkeeping and calculations. HBK 2255 and Building Acoustics Partner allow users to gain the benefits of this method in the simplest and most efficient way possible.


Related blog articles

About HBK

Accelerate your product innovation with HBK solutions in virtual, physical and in-process testing.  From the electrification of mobility to the advancement of smart manufacturing, we support you throughout the entire product lifecycle, sharing your mission for a cleaner, healthier, and more productive world.